While the plant operator's license exam does not have a great number of distribution questions, it is clear that operators are expected to have basic knowledge of distribution systems. We are listing the most frequently asked questions and their answers. Those in bold type are most often found on the plant operator's exam.
updated 23 hours ago by TKNotecards
show moreless
Page to share:
Embed this setcancel
COPY
code changes based on your size selection
Size:
X
Show:

1

What is the minimum pressure required in the distribution system?

20 psi

2

The distribution system must have a minimum of _mg/L in the distribution mains.

0.2 mg/L

3

What is the minimum combined residual for the distribution system?

0.6 mg/L

4

What is the maximum free or combined chlorine residual in the distribution system?

4 mg/L

5

Valves on distribution mains should be how far apart?

800-1,000

6

How far apart are fire hydrants in residential areas?

500'

7

Fire hydrants in commercial areas should be how far apart?

No more than 300' from any part of a commercial building

8

How often should water main valves be exercised?

At least once a year

9

What is the main purpose of water storage tanks?

card image

10

What is the configuration of a standpipe?

It is taller than it is wide

11

How many feet apart should a ladder be in a trench?

No more than 25' from any worker

12

How many ladders will you need for a 100' trench?

2 (25' from each end)

13

How far out of the trench should the ladder extend?

30"

14

When belled pipe is being installed, the bells are usually pointed in the direction that the work is heading except when the pipe is headed downhill, then the bell should?

Face uphill

15

How many feet from trench should the spoil bank be placed?

Minimum of 2 ft.

16

Excavations five feet or deeper must be?

Shored

17

Before doing any excavation work, you must?

Call for/Get Underground Locations

18

Any excavation or tank four feet or deeper is considered?

A Confined Space

19

Barricades with diagonal stripes must have the stripes?

Sloped toward traffic

20

When a pipeline changes direction or sizes, at dead ends, and when valves or hydrants are closed rapidly ______ must be installed?

Thrust Blocks

21

Water mains should be installed at least ______ horizontally from sewer mains.

10'

22

Water mains should be installed at least ______ higher than a sanitary sewer pipe.

1'

23

Surge Tanks are used to control?

Water Hammer

24

Where are air relief valves located in a distribution system?

At High Points

25

Hydropneumatic tanks should be equipped with?

Relief Valves

26

What type of valve is located at a point that is below the hydraulic gradient?

Altitude Valve

27

When should storage tanks be taken out of service for maintenance?

During periods of low demand

28

How do you disinfect the interior of a storage facility?

Spray or brush interior with a 200-PPM Cl₂ Solution

29

What is the minimum chlorine dosage to disinfect a newly installed main?

25 mg/L for 24 hours

30

The most commonly used joints on installed pipes are?

Push on joints

31

When should fire hydrants be inspected and serviced?

Twice a year

32

Where is the operating valve located in a dry barrel fire hydrant?

At the bottom

33

Distribution mains should be installed in a ог design to avoid dead ends?

Grid or Looped System:

34

What is a wet tap?

Installation/tap made under pressure

35

When a pipeline has been installed, the first layer of backfill is compacted to which point?

Up to the horizontal centerline of the pipe

36

A newly installed main is tested at a pressure higher than expected operating pressure or ________ psi for 24 hours?

50%, 250 PSI

37

What is measured after the completion of the pressure test?

Water loss or leakage

38

What is the chief purpose for of storage tanks?

To meet peak hourly demand