front 1 What is the minimum pressure required in the distribution system? | back 1 20 psi |
front 2 The distribution system must have a minimum of _mg/L in the distribution mains. | back 2 0.2 mg/L |
front 3 What is the minimum combined residual for the distribution system? | back 3 0.6 mg/L |
front 4 What is the maximum free or combined chlorine residual in the distribution system? | back 4 4 mg/L |
front 5 Valves on distribution mains should be how far apart? | back 5 800-1,000 |
front 6 How far apart are fire hydrants in residential areas? | back 6 500' |
front 7 Fire hydrants in commercial areas should be how far apart? | back 7 No more than 300' from any part of a commercial building |
front 8 How often should water main valves be exercised? | back 8 At least once a year |
front 9 What is the main purpose of water storage tanks? | back 9 ![]() |
front 10 What is the configuration of a standpipe? | back 10 It is taller than it is wide |
front 11 How many feet apart should a ladder be in a trench? | back 11 No more than 25' from any worker |
front 12 How many ladders will you need for a 100' trench? | back 12 2 (25' from each end) |
front 13 How far out of the trench should the ladder extend? | back 13 30" |
front 14 When belled pipe is being installed, the bells are usually pointed in the direction that the work is heading except when the pipe is headed downhill, then the bell should? | back 14 Face uphill |
front 15 How many feet from trench should the spoil bank be placed? | back 15 Minimum of 2 ft. |
front 16 Excavations five feet or deeper must be? | back 16 Shored |
front 17 Before doing any excavation work, you must? | back 17 Call for/Get Underground Locations |
front 18 Any excavation or tank four feet or deeper is considered? | back 18 A Confined Space |
front 19 Barricades with diagonal stripes must have the stripes? | back 19 Sloped toward traffic |
front 20 When a pipeline changes direction or sizes, at dead ends, and when valves or hydrants are closed rapidly ______ must be installed? | back 20 Thrust Blocks |
front 21 Water mains should be installed at least ______ horizontally from sewer mains. | back 21 10' |
front 22 Water mains should be installed at least ______ higher than a sanitary sewer pipe. | back 22 1' |
front 23 Surge Tanks are used to control? | back 23 Water Hammer |
front 24 Where are air relief valves located in a distribution system? | back 24 At High Points |
front 25 Hydropneumatic tanks should be equipped with? | back 25 Relief Valves |
front 26 What type of valve is located at a point that is below the hydraulic gradient? | back 26 Altitude Valve |
front 27 When should storage tanks be taken out of service for maintenance? | back 27 During periods of low demand |
front 28 How do you disinfect the interior of a storage facility? | back 28 Spray or brush interior with a 200-PPM Cl₂ Solution |
front 29 What is the minimum chlorine dosage to disinfect a newly installed main? | back 29 25 mg/L for 24 hours |
front 30 The most commonly used joints on installed pipes are? | back 30 Push on joints |
front 31 When should fire hydrants be inspected and serviced? | back 31 Twice a year |
front 32 Where is the operating valve located in a dry barrel fire hydrant? | back 32 At the bottom |
front 33 Distribution mains should be installed in a ог design to avoid dead ends? | back 33 Grid or Looped System: |
front 34 What is a wet tap? | back 34 Installation/tap made under pressure |
front 35 When a pipeline has been installed, the first layer of backfill is compacted to which point? | back 35 Up to the horizontal centerline of the pipe |
front 36 A newly installed main is tested at a pressure higher than expected operating pressure or ________ psi for 24 hours? | back 36 50%, 250 PSI |
front 37 What is measured after the completion of the pressure test? | back 37 Water loss or leakage |
front 38 What is the chief purpose for of storage tanks? | back 38 To meet peak hourly demand |